|
Water
Coolant Loop System
The WCLS provides thermal conditioning of the crew cabin by collecting
heat at the cabin-air-to-water-coolant-loop heat exchanger and
transfers heat to the water coolant loops. The water coolant loops
transfer the heat at the water and Freon-21 coolant loop interchanger.
The WCLS also provides thermal conditioning for the three avionics
bays by an air-to-water heat exchanger in each avionics bay, the
cabin heat exchanger, liquid-cooled garament and water chiller,
which transfers heat to the water coolant loops. The IMU air-to-water
heat exchanger also transfers heat to the water coolant loops.
There are two complete and separate water coolant loops that
flow side by side and can operate at the same time. The only difference
between water coolant loops 1 and 2 is that loop 1 has two water
pumps and loop 2 has one pump.
Some electronic units in each of the avionics equipment bays
are mounted on cold plates. The water coolant loops flow through
the cold plates, and the heat generated by the electronics unit
is transferred to the cold plate and then to the water coolant
loop, which carries heat from the electronic unit. The cold plates
mounted on the shelves in each avionics equipment bay are connected
in a series-parallel arrangement with respect to the water coolant
loop flow.
The water pumps in coolant loop 1 are controlled by the H2O pump
loop 1 A and B switch on panel L1 in conjunction with the H 2
O pump loop 1 GPC off and on switch on panel L1. The GPC position
enables the general-purpose computer to command the loop 1 pump,
which is selected by the H2O pump loop 1 A or B switch, to circulate
water through water coolant loop 1. The on position energizes
the loop 1 pump. A ball-type check valve downstream of each water
pump prevents reverse flow through the non-operating pump. The
off position removes electrical power from both the A and B pumps
of loop 1.
Water pump 2 is controlled by the H 2 O pump loop 2 GPC on, off
switch on panel L1. When the switch is positioned to GPC , water
pump 2 is commanded by the GPC to circulate water through water
coolant loop 2. The on position energizes the water pump 2 to
circulate water through water coolant loop 2. The off position
removes electrical power from water coolant loop 2 pump.
Water loops 1 and 2 flow side by side through the same areas
when both loop pumps are in operation. Downstream of the water
pump in each loop, water flow splits into three parallel paths:
one through the avionics bay 1 heat exchanger and cold plates;
another through the avionics bay 2 heat exchanger and cold plates,
payload bay floodlight cold plates and thermal conditioning of
the crew cabin windows; and the third through the crew cabin multiplexer/demultiplexer
flight deck cold plates, the avionics bay 3A heat exchanger and
cold plates and avionics bay 3B cold plates. The three parallel
paths in each coolant loop then rejoin.
The water coolant loops 1 and 2 flow toward the Freon-21 coolant
loops 1 and 2 and water heat exchanger and split into two parallel
paths. One parallel path in each water coolant loop flows through
the Freon-21 coolant loops 1 and 2 and water interchanger, liquid-cooled
garment heat exchanger, potable water chiller, cabin heat exchanger
and IMU heat exchanger to the respective water coolant loop 1
and 2 pump. The other parallel path in each water coolant loop
flows to a water coolant loop bypass in that loop.
The bypass controller in each water coolant loop is enabled by
its corresponding H2O loop 1 and 2 bypass mode auto/man switch
on panel L1. When a coolant loop's H 2 O loop bypass mode auto/man
switch is positioned to auto , the water bypass controller and
bypass valve automatically control the amount of water in the
coolant loop that bypasses the water/Freon-21 coolant loop interchanger.
When the bypass controller's outlet temperature is 65.5 F, the
loop's bypass valve is fully closed, and the excess heat in the
loop is transferred to the corresponding Freon-21 coolant loop
at the coolant water interchanger. Cooled water flows through
the LCG heat exchanger, cabin heat exchanger and IMU heat exchanger,
which joins with the bypass flow parallel path. When the bypass
controller senses that the coolant loop water pump's outlet temperature
is 60.5 F, the controller bypasses a maximum amount of water around
the Freon-21 coolant loop/water interchanger and allows the water
at that coolant loop pump to be warmed from the parallel path
of water flowing from the interchanger and corresponding LCG heat
exchanger, cabin heat exchanger and IMU heat exchanger. When the
H2O loop bypass mode auto/man switch for the coolant loop is positioned
to man , the flight crew sets the corresponding H2O loop man incr/decr
switch on panel L1 to manually control the bypass valve in that
water coolant loop.
Because of changes in heat loads from the initial design, the
water bypass controllers are not able to control temperatures
automatically as originally intended. As a result, the water bypass
control valve is manually controlled by the flight crew by positioning
the H 2 O loop bypass mode auto/man switch in man and the H 2
O loop bypass man incr/decr switch for that water coolant loop
on panel L1. The bypass valve is adjusted before launch to provide
a flow of 900 to 1,000 pounds per hour through the Freon-21 coolant
loop/water interchanger, and the control system remains in the
manual mode for the entire flight.
The accumulator in each water coolant loop provides a positive
pressure on the corresponding water pump inlet and accommodates
thermal expansion and dampening pressure surges in that water
coolant loop when the pump is turned on or off. Each accumulator
is pressurized with gaseous nitrogen at 19 to 35 psi.
The pressure at the outlet of the water pump in each water coolant
loop is monitored and transmitted to the H 2 O pump out press
loop 1 and loop 2 switches on panel O1. When the switch is positioned
to loop 1 or loop 2, the corresponding water coolant loop's pressure
is monitored on the H 2 O pump out press meter on panel O1 in
psia.
The yellow H2O loop C/W light on panel F7 will be illuminated
if the outlet pressure of the water coolant loop 1 pump is below
45 psi or above 79.5 psi or if the outlet pressure of the loop
2 pump is below 45 psi or above 81 psi. The pump inlet and outlet
pressure of each coolant loop is monitored and transmitted to
the systems management GPC for CRT readout.
In summary, with the crew cabin's structural thermal capacity,
its temperature will not exceed 95 F during entry or until flight
crew egress.
|